Universal complete transformer Substation 35(20)/0.4 kV (KTPU)
Universal package transformer substation of KTPU series for 35(20)/0.4 kV is designed to receive, transform, and distribute three-phase alternating-current electric power with a commercial frequency of 50 Hz. The best solution is to use it for feeding small-size and remote facilities, where it is impossible to construct 220(110, 35)/6(10) kV step-down substations.
The following equipment is used in 35(20)/0.4 kV universal package transformer substation:
- power transformer of TMG (TM) series with a capacity of 25, 40, 63, 100, 160, 250, 400 or 630 kVA;
- surge arresters of OPN-P series;
- polymer or porcelain insulators;
- disconnector of RGPZ 1-II-35/1000 UKhL1 (NF1 as per IEC) series.
The design features and advantages of 35(20)/0.4 kV KTPU are as follows:
- Electromechanical and electric interlocks are provided for in the substation.
- All required protection means are installed in KTPU against: atmospheric (lightning) overvoltage and switching overvoltage; line-to-line faults; overcharging and line-to-line faults on 0.4 kV lines.
- High degree of prefabrication allows quickly installing the substation on a new place.
- Easy maintenance and serviceability.
- Made with a cabled or aerial outlet on the 0.4 kV side.
- Reduced weight and size parameters.
Parameter name
|
Value
|
---|---|
Power transformer capacity, kVA
|
25; 40; 63; 100; 160; 250; 400; 630
|
Rated (linear) voltage on the high-voltage side, kV
|
35(20)
|
Maximum operating voltage on the high-voltage side, kV
|
42(24)
|
Rated voltage on the low-voltage side, kV
|
0.4
|
Rated fuse current (rating), kA
|
2.5; 8; 10; 16; 20; 31.5
|
Rated breaking current, kA
|
8
|
Short-time thermal current, kA:
·on the HV side (high-voltage device)
·on the LV side (low-voltage switchgear)
|
8
12.5
|
Short-time electrodynamic current, kA:
·on the HV side (high-voltage device)
·on the LV side (low-voltage switchgear)
|
20
31
|
Protection rating as per GOST 14254:
·for low-voltage switchgear
·for other components
|
IP34
IP00
|
Winding circuit and vector group of transformer
|
Y/YN-0; Δ/YN-11
|
Sound level, no higher than, dBA
|
60
|
Overall dimensions, no more than, mm
length x width x height
|
4000х2500х4700
|
Weight, no more than, kg
|
5000
|
Made in accordance with the Corporate Standard Ts 00212883 - 021:2014.