RGP-110 series horizontal rotary disconnector for 110 kV
The outdoor horizontal rotary AC disconnector of RGP-110/1250 (2000) NF1 series with drives of PR-K, PR-M, PD, PDS and more types is designed for closing and opening electrically dead high-voltage electric circuit sections as well as for grounding deenergized sections by using stationary grounding blades, which ensures safe operation at the deenergized section. Climatic category is UKhL (temperate and cold weather) according to GOST 15150 (NF according to IEC); placement category is 1 according to GOST 15543.1 for disconnectors with protection rating of IP00 according to GOST 14254-96.
RGP-110 series disconnectors are manufactured in single-pole, two-pole, and three-pole versions with longitudinal arrangement of the poles (keel-type).
The following versions of RGP-110 series disconnectors are manufactured:
- RGPZ-1-110/1250(2000) NF1, with one grounding blade on the master column side;
- RGPZ-2-110/1250(2000) NF1, with two grounding blades;
- RGP-110/1250(2000) NF1, without grounding blades.
The insulation of each pole consists of two insulators. Depending on the disconnector version, insulators of various degrees of insulation are used. Upon customer’s request, disconnectors can be supplied with other types of insulators.
The horizontal rotary disconnectors are manufactured based on the drawings and technology developed by the “Electroschield TM-Samara” Group of Companies.
Made in accordance with the Corporate Standard Ts 18726720-012:2014.
The product has been certified by the National Certification System of the Republic of Uzbekistan and
Certification System of the Russian Federation (GOST-R).
Technical specifications:
Parameter name
|
Single-pole
|
Two-pole with parallel arrangement of poles
|
Three-pole longitudinal arrangement of poles
|
||
Rated voltage, kV
|
110
|
||||
Maximum operating voltage, kV
|
126
|
||||
Rated current Ir, A
|
1250(2000)
|
||||
Rated short-time withstand current (short-time thermal current) IT, kA
|
25(40)
|
||||
Rated short-time withstand current lead time (short-circuit time), sec.:
- for main blades
- for grounding blades
|
3
1
|
||||
The highest peak of the rated short-time current (short time electrodynamic current), Id, kA
|
63(102)
|
||||
Permissible mechanical load on the lead-outs from the wires connected taking into consideration the effect of wind loads (wind speed of up to 15 m/s) and ice formation (ice sheet thickness of up to 10 mm), no less than, N
|
800(1000)
|
||||
The highest force applied to the drive, at operating arm’s length together with an extension of 1.5 m, no more than, N
|
245
|
||||
Overall dimensions of the disconnector, no more than, mm
- length
- width
- height
|
1790
610
3300
|
4610
1790
3300
|
7685
695
3300
|
||
Weight of the disconnector, no more than, kg
|
475(490)
|
940(1030)
|
1261
|